TYPE:General: Rectangular designed basin/enclosure with a vertically stacked series of inclined horizontal slats/baffles, or honeycomb grill, arranged around the sides. Hot process water, which needs cooling, is pumped over the slats, creating a cascading acti
MODEL :Field erected 4 Cells.
STYLE :Induced Updraft. Counter Flow. Open Loop.
CAPACITY-TONS:8500 Tons nominal per cell depending on temps & GPM
CAPACITY-GPM:16000-19200GPM [Design 21430GPM]
TEMP.(H2O)-IN:100 Deg F [87-115Deg F depending on GPM & Wet Bulb]
TEMP.(H2O)-OUT:84Deg F @ Wet Bulb 60 Deg F nominal [Temp out 71-91.5 Deg F depends on GPM, inlet temp and Wet bulb variable 48-72 Deg F in last svc.] 16-24Deg F Delta T.
FAN(S):1 @ 10 blade ~25'Dia. Adjustable pitch.
AIRFLOW-CFM:100-127RPM variable fan speed.
MATLS.CONSTRN-UPPER:SS/FRP support. FRP sides. Fill material PVC, 6ft deep bed & top drift eliminators PVC [tbc]
MATLS.CONSTRN-PAN:Open concrete.
PRIOR SERVICE:Power plant Steam Turbine Generator cooling water. Delta T- Approach 24Deg F, Range 16Deg F. @ 16580GPM flow
COMMENTS:4 modular cells total 64-76800GPM duty. 10 @ ~25ft dia adjustable pitch fan blades per cell. Stairway at one end, caged ladder at side and opposite end, top platform and handrails for bank of 4 cells. Installed dimensions [4 cells] approx 45ft high x 45ft
SHIPPING SIZE-W X H X L:12'W X 11''H X 50'L [8-10 truck loads per cell including fill]