TYPE:Finned tube type heat exchanger, air flow cooled or heated as passes over finned tube bundle mounted in ducted housing via liquid medium in tubes.
MODEL:C-175-10
AREA-BARE TUBE:175SF [tbc]
AREA-EXTENDED:500SF approx
MAT'L CONSTRN-TUBES:SS throughout except Cu, manifold.
TUBES:3/4"dia [tbc] 30" long, hairpin bundle, horizontal in housing.
FINS:Aluminum, 8.5 Fins/inch approx. Fins are single sheets, configured to housing full cross section.
HEADERS:Tubes 1-1/2" in/out. Housing 10" wide, flat tubesheet flanged and bolted, horizontal removable bundle with hairpin tube groups..
PRESSURE-MAX:Tubes 100# @ -70/+200 Deg F. Hyd 150#
SECTIONS PER BAY:1.
NO. BAYS:1
FANS:NA
DRIVEN BY:NA
DRIVEN VIA:Direct
PRIOR SVC:Total heat exchanged 194637Btu/Hr approx. 1000CFM Air flow 290Deg F in, 100Deg F out, velocity 470Ft/Min @ 24.7 PSI. In Water Cooling service 39 GPM @ inlet temp 85Deg F, discharge 95Deg F.
COMMENTS:Horizontal SS housing, Right hand design. Shipping size 20''W x 36'''H x 4'6''Long, Wt.350#